The FX2200CF range of conventional control panels provide a solution to any conventional system requirement. The advanced features include a simple “one-shot” user test facility, class change contacts, battery voltage alarms and charger temperature compensation, all included as standard to ensure ease of use and high reliability.

Category: Tags: ,

Description

The FX2200CF range of conventional control panels provide a solution to any conventional system requirement. The advanced features include a simple “one-shot” user test facility, class change contacts, battery voltage alarms and charger temperature compensation, all included as standard to ensure ease of use and high reliability.

Attention to detail is emphasised by the neat log book holder feature, allowing essential records to be stored close to hand, ready for quick reference.

For larger installations, custom configuration of the panels offers even greater flexibility, allowing project specific requirements to be easily met, in a competitive and cost effective package.

Features

  • 2, 4 or 8 zones panels
  • Flexible, high specification system
  • Surface or semi-flush mounting
  • Simple “one-shot” autoreset user test facility
  • Maintenance free poly switch circuit protection, with auto reset
  • Class change and programmable fire/fault relay as standard

Benefits

  • Suitable for a large range of projects
  • No fuses required
  • Discreet panel design for incorporation in to any decor
  • Numerical access code (no lost keys)
  • Easy to maintain/service

Specification

Model

FX2202CF

FX2204CF

FX2208CF

Standards

EN54-2 1997, A1: 2006 EN54-4 1997, A1: 2002 & A2: 2006

Number of zones

2

4

8

Detectors per zone

32

Number of alarm circuits

2

4

Alarm circuit load

150mA per circuit 0.3A total

400mA per circuit 0.8A total

500mA per circuit 2A total

End of line devices

Detection circuits: EOLM1 monitoring unit. Alarm lines: 6.8K resistor

Auxiliary fire / fault output

signal 5A 24V DC single pole changeover contacts

Auxiliary DC output

24V DC fused. 30mA

Repeater port

No

Yes

Mains input voltage

230V AC –10% +15%

System operating voltage

24V DC

Standby duration

24 hours

Battery (sealed lead acid)

1 x 3.2 AH

2 x 3.2 AH

Recharge period

24 hours

Panel construction

Polycarbonate housing & back box

Cable entries

Top: 12 x 20mm entries with blanking plugs – Rear cable entry aperture

Environmental rating

IP30. -5°C to +40°C humidity 75% max (non condensing)

Surface dimensions WxHxD (mm)

332 x 270 x 90mm